In this Tip of the Month, we will compare the performance of a simple refrigeration system with another one employing a flash economizer. Specifically, we will evaluate compressor power saving, the effects of compressor suction–line pressure drop and the interstage pressure drop on compressor power requirement and condenser duty.

The objective of a refrigeration system is to “pump” low temperature heat from the process fluid to high temperature (ambient) where it is rejected to the environment. Energy is required to pump heat. The amount of energy depends on the quantity of heat to be “pumped’ (chiller duty) and how far the heat has to be pumped (temperature difference between the chiller and the condenser). Compression refrigeration is by far the most common mechanical refrigeration process. It has a wide range of applications in the gas processing industry. It provides chilling for:

  1. NGL extraction, LNG production, and LPG product storage
  2. Hydrocarbon and water dew point control
  3. Reflux in deethanizers/demethanizers

The details of a simple single-stage refrigeration system and a two-stage refrigeration system employing one flash tank economizer are given in Chapter 16 of Gas Conditioning and Processing, Volume 2 [1]. The process flow diagrams for the simple and with flash economizer refrigeration systems are shown in Figure 1. Note that provisions have been made to consider pressure drop in different segments of the loops.

Process Flow Diagram

Figure 1. Process flow diagram for the simple and flash economizer refrigeration systems

Let’s consider removing 1.0×107 kJ/h (2778 kW) from the process gas at -35°C and rejecting it to the environment by the condenser at 35°C. Assuming 5 kPa pressure drop in the chiller, the compressor suction pressure is 132.4 kPa. The condenser pressure drop plus the pressure drop in the line from the compressor discharge to the condenser was assumed to be 50 kPa; therefore, compressor discharge pressure is 1270 kPa. Pure propane is used as the working fluid. The effect of impurities in the working will be discussed in the future Tip of the Month. In this study, all of the simulations were performed by HYSYS software [2].

For the case of with flash economizer and assuming no pressure drop between the two stages and in the suction line, Figure 2 presents the variation of the compressor interstage and total power as a function of the interstage pressure. As can be seen in this figure, the optimum interstage pressure is about 490 kPa. This pressure corresponds to the minimum total power. However, the ideal optimum interstage pressure based on equal compression ratio can be found by Equation kPa. Figure 3 also presents the locations of these two optimum pressures.

Figures 2 and 3

In order to study the effect of pressure drop in the compressor suction line on the total power requirement and condenser duty, the interstage pressure drop was set equal to zero. The suction line pressure drop was varied from 0 to 30 kPa with an increment of 10 kPa. Two sets of simulations were performed:

  1. The interstage pressure was determined based on the equality of compression ratio
  2. The interstage pressure was determined by minimizing the total compressor power

In each case, the total compressor power for the flash economizer system was compared with the power requirement for the simple refrigeration system and the percent of power savings were calculated.

Next, the effect of the interstage pressure drop on the total compressor power requirement and condenser duty was investigated. This was done by setting the compressor suction line pressure drop to 30 kPa and varying the interstage pressure drop from 0 to 40 kPa by an increment of 10 kPa. The load of interstage pressure drop was equally distributed between the two stages of compression. Again, the simulation results of flash economizer were compared with those of the simple refrigeration system. The summary of the results is shown in Table 1. Figures 4 and 5 are the graphical representation of the results presented in Table 1.

Table 1. Comparison of the results based on the equality of compression ratio and minimizing the total power requirement

Table 1

Table 1 indicates that the power saving ranges from 12.7 to 16.1 % when a flash economizer is used in place of the simple refrigeration system, using interstage pressure based on the equality of compression ratio. However, if the interstage pressure is determined based on minimizing the total compressor power requirement, the power saving will be from 14.4 to 16.5 %. The interstage pressure drop is unique to flash economizer and its effect is the reduction of the power saving when compared to the simple refrigeration system and increases the condenser duty.

To learn more about similar cases and how to minimize operational problems, we suggest attending our G4 (Gas Conditioning and Processing) and G5 (Gas Conditioning and Processing – Special) courses.

By Dr. M. Moshfeghian

Figures 4 and 5

Reference:

  1. Campbell, J.M., “Gas conditioning and Processing, Vol 2: The Equipment Modules”, 8th Edition, Edited by R.A. Hubbard, John M. Campbell & Company, Norman, USA, 2000.
  2. ASPENone, Engineering Suite, HYSYS Version 2006, Aspen Technology, Inc., Cambridge, Massachusetts U.S.A., 2006.
Did you enjoy this post? Do you have a question?
Leave us a Comment below!

Want to read more articles like this?
Subscribe to our RSS Feed or visit the Tip of the Month Archives for past articles.